If any problem in one bus the BB protection relay will trip the CB's in fulty Bus and also Bus coupler and Bus section breakers.
If any problem in opening of Bus coupler or bus section breakers the after 100ms (ABB -REB500) & 250 ms ( Siemens) the relay will transfer the Trip to other buses.
This time delay need for other BF & PD scheme also.
Under frequency trip will not given to BF initiation . Because the BF relay current setting will be full 1 Amps and during under frequency trip condition there is no changes in normal current. If U/F trip given to BF it will not operate.