230kV RATED SF6 GAS PRESSURE

Normal condition ( At 20 dec Tem)
CB - 0.630 Mpa
VT - 0.630 Mpa
OTHERS ( ES, DS, GIB ) - 0.550 Mpa
Pressure Alarams in density Detector
Stage -I Gas Leakage Alaram
CB - 0.605 Mpa
VT - 0.605 Mpa
OTHERS ( ES, DS, GIB ) - 0.495 Mpa
Stage -II Gas Leakage Alaram
CB - 0.560Mpa
VT - 0.560 Mpa
OTHERS ( ES, DS, GIB ) - 0.450 Mpa
High pressure Alaram
OTHERS ( ES, DS, GIB ) - 0.620 Mpa