The concentration of SO2 is an indicator for the
presence of decomposition products in SF6 gas. The SO2 measurement in SF6
gas in the GIS equipment which is energized condition is easy way to analyze
the abnormalities.
Gastec Detector Tubes
|
Gastec Tube
|
Gastec Detector Tubes are used for the rapid
measurement of SO2 in SF6 gas. These Pre-calibrated, direct-read detector tubes
offer distinct lines of demarcation for easier viewing and color charts. Each
tube contains detecting reagents that are especially sensitive to the target
substance and quickly produces a distinct layer color change.
Gastec Gas Sampling Pumps
Gastec Gas Sampling Pumps are used to take the sample of SF6 gasCollect the SF6 gas in a polythene bag from the equipment Non returnable value. Take a fresh Detector Tubes and broke two edges and fix one edge with Gas sampling pump, insert the other end in to gas collected polythene bag. Then pull the gas Pump handle. Now gas will accumulated in the gas tube. If SO2 presence in the SF6 gas, the tube in side Blue color will be change in to Yellow.