THE STORY OF TRANSFORMER STABILITY


The transformer stability test used to conform the CT connections for Differential and REF protection. This test also used as a primary injection test for HV & LV side BCT's.


Example   Transformer Data

Voltage Ratio :             230/ 34.5/13.8 kV
MVA Rating :              100/133 MVA                                                                                                                  
Vector Group:             YNyn0(d5)
% Impedence :             12.24 @ 100 MVA BASE.


CALCULATION TO FIND THE PRIMARY AND SECONDARY CURRENT


PRIMARY SIDE : -

HV side full load current  =  Power /  √3 x Voltage = 100×10^3            =  100000000 = 251 Amps
                                                                                √3 × 230× 1000        399050

HV side Impedence    =   HV side Voltage              =   230× 1000  = 916 Ohms
                                          HV side full load current       251

HV side Impedence/ Phase =  HV side Impedence X % Impedence = 916 X 12.24  =  112 Ohms
                                                                                                                          100

HV side current / Phase    =  Applied Voltage / HV side Impedence/ Phase

                                        = 380 / 112 =  3.38 Amps


 LV side SIDE : -

Transformer Ratio = 230/ 34.5 = 6.66

LV side current = 6.6666* 3.38 = 22.53 Amps
                                                                                                             

TEST -1 Three Phase Balanced Injection


Test connection: Three phase short circuit outside protected zone on 34.5kV side. Three phase voltage injected on HV side = 380V

The balanced current can measured in the relay as follows 
                                                            
Relay - Primary Current (A)
HV
LV
3.326<0°
22.201<181.141°
3.205<241.5°
22.935<59.28°
3.288<121.5°
23.573<299.34°

Note : -


1. LV current 180 dec phase sifted from HV current.

2. No return current in Neutral 

TEST -2 Three Phase Unbalanced condition



To make this condition open any one of CT FT fingers and short by insert the FT jack. 

The Unbalanced current can measured in the relay as follows 

Relay- Primary Current (A)
HV
LV
0.00
21.985
0.00
22.226
0.00
22.265

TEST -3 Three Phase REF balanced condition

Test connection: Three phase short circuit outside protected zone on LV side. Single Phase Injection was done one by one  on the primary to check the stability and sensitivity.

1. No return current in Neutral 
2. During single phase injection voltage will developed  in the one phase Tertiary winding. If winding is connected with ground  a circulating current will flow through ground during stability.


TEST -4 Three Phase REF Unbalanced condition

 Polarity of the neutral BCT was reversed at the protection panel to simulate the unstable condition.


TEST -5 BCT primary injection


PRIMARY INJECTION HV & LV  WINDING :


Test connection: Three phase short circuit outside protected zone on LV side. Three phase voltage injected on HV side = 380V 

PRIMARY INJECTION TERTIARY  WINDING :

Test connection : The shorting and grounding bar was removed from the Delta winding and current was injected with Severker Test Kit and secondary currents were measured in the Transformer LCP panel.






                                     