Monday, July 29, 2013

TRIPPING FOR NO FAULT & NO TRIPPING FOR FAULT


TRIPPING FOR NO FAULT

Transformer Earth fault protection was operated when load increasing.
Then investigation started and team checked all power cables transformer IR value. Then primary injection test was done and found "B" phase CT secondary wire loose connection. " B" phase current not reached to relay and residual current developed. Residual current flow  through neutral coil and earth fault operated during load condition only.












 NO TRIPPING FOR FAULT

Transformer Earth fault protection was operated during fault condition. After investigation found the secondary wire going to neutral protection coil was ground and residual current taken essay path to return. So neutral trip coil not getting the fault residual current to trip the breaker.



Sunday, July 28, 2013

TRIPPING CIRCUIT PROBLEM

380KV HYUNDAI 380KV CB TRIPPING CIRCUIT PROBLEM

During trip the breaker from trip relay (LOR) Pole Discrepancy Stage-1 was operated.
After investigation the following point were observed.

1.The overall trip circuit length more than 300 mts.
2.The resistance of the circuit loop 14 ohms. ( Resistance measurement refer drawing)
3. Resistance of trip coil unit ( Coil + Stabilizing resistance + Capacitor ) 40 ohms.
4. Trip circuit cable size 2.5 Sqmm.
5. Trip circuit voltage used 127 dc.

As per stranded minimum operating voltage of trip coil is 70 v dc.

Due to more loop resistance and coil resistance voltage drop was more in the trip circuit. So during tripping operation ( by operating last lockout of the circuit) trip coil not getting enough voltage to trip the breaker and PD operated immediately ( Pole Discrepancy Stage-1 lock out relay very near to the trip coil).

We are decided to reduce the loop resistance of the trip circuit by increasing the cable size upto 12 Sq.mm. ( ( 2 x 6Sq.mm).

The loop resistance was reduced upto 8 to 9 ohms from 14 ohms and circuit was worked properly.

But this is the temporary  solution and permanent solution is reduce the trip coil unit resistance from 40 ohms to below 20 ohms.



 















Resistor & Capacitor unit








Sunday, June 9, 2013

380kV LINE VT FAIL

380 kV fail due to over voltage















The line VT rated 400KV for continuous  charging. Line length is more than 300 km. The voltage in sending end was 409 kv and due to line capacitance the  received end voltage was 420kv .

Because of over voltage the lie VT get damaged. The following protections are operated.

RED670

1. Zone-1,2,3 start
2. Zcom -Trip
3. DEF start
4. Fuse fail


Micom 546

1. 21-2 SEND
2. 67N - SEND
3.21-2 RECV
4. 67N - RECV















PROTECTION FOR SPARE LINE




















The spare line portion can protect as below during temporary Energization or close the all cross bay CBs to connect 1A and 2A buses. 

There are two way to protect this portion 

1. Take any spare CT below the middle breaker for Bus bar protection to cover the spare line.
2. Enable the Over current and Earth Fault with 0.2 or 0.4 minimum setting in the Breaker failure relay.


Tuesday, May 28, 2013

REACTOR STABILITY





1. Reactor rated current will be 121 Amps for rated voltage of 380kv .

2.So need more voltage for stability test in primary side.

3. As per above calculation primary current is 0.5 apms. So secondary will be mili amps.

4. The measurement of low mili amps is very difficult. So measure the voltage develop access the relays.

5. Adjust the output voltage of Generator to maximum value. Feed through a set up transformer get good voltage value.












About Me

My photo
THIS IS SIVA T&C ENGINEER IN NCC LTD - SAUDI.