Sunday, June 9, 2013

380kV LINE VT FAIL

380 kV fail due to over voltage















The line VT rated 400KV for continuous  charging. Line length is more than 300 km. The voltage in sending end was 409 kv and due to line capacitance the  received end voltage was 420kv .

Because of over voltage the lie VT get damaged. The following protections are operated.

RED670

1. Zone-1,2,3 start
2. Zcom -Trip
3. DEF start
4. Fuse fail


Micom 546

1. 21-2 SEND
2. 67N - SEND
3.21-2 RECV
4. 67N - RECV















About Me

My photo