KVS100 SYN RELAY CB INPUT
How to give CB input to KVAS100 SYN check relay to start the syn check function ?
LOGIC FUNCTION ----------- SCHEME Fn Links-1 -------- set 000000000100011
INPUT Start chsyn ------------00000001
48 DC voltage available in relay
Take +ve voltage connect with CB "b" contact (NC)
When CB is open relay will start the Syn function give permit to close the CB
Relay will reset when CB is closed.
FIBER OPTIC CABLES
FIBER OPTIC CABLES USED FOR LINE DIFFERENTIAL AND DRP PANEL
MAKE: OPTOKON CO . LTD
MULTIDUPLEX
J-V (ZN) H 2G 62.5/125 BLUE (2.8 mm) (850 nM)
PATCH CORD TERMINATION
Friday, December 24, 2010
TESTING TIPS -2
Voltage for fuse failure relay should take at final stage of the voltage circuit.
It will block the operation of the main relay if any open wiring and faultily FT switch open operations.
Monday, December 20, 2010
DESIGN TIP -1 CT CIRCUIT
1.CT secondary star point should be equipment side and P2 should be equipment side.