Saturday, February 19, 2011
Wednesday, February 16, 2011
KVS100 SYN RELAY CB INPUT
How to give CB input to KVAS100 SYN check relay to start the syn check function ?
LOGIC FUNCTION ----------- SCHEME Fn Links-1 -------- set 000000000100011
INPUT Start chsyn ------------00000001
48 DC voltage available in relay
Take +ve voltage connect with CB "b" contact (NC)
When CB is open relay will start the Syn function give permit to close the CB
Relay will reset when CB is closed.
FIBER OPTIC CABLES
FIBER OPTIC CABLES USED FOR LINE DIFFERENTIAL AND DRP PANEL
MAKE: OPTOKON CO . LTD
MULTIDUPLEX
J-V (ZN) H 2G 62.5/125 BLUE (2.8 mm) (850 nM)
PATCH CORD TERMINATION
Subscribe to:
Posts (Atom)